Geo heat pump 48-112 kW

Industrial Line EcoTouch 5110T | 57-238 kW

Hot water Ventilation Cooling Heating Solar
Industrial Line EcoTouch 5110T - Geo heat pump 48-112 kW +
  • Heat pump with middl energy demand
  • Power adjustment 50/100 %
  • Intuitiv controll software EasyCon
  • Sensor system
  • COP-Counter and display all operation data
  • Domestic water heater, external tank
  • Chlorine-free, environment-friendly refrigerant R410A
  • Output signal for speed regulation of the circulate pumps
  • Modular design for optimised installation
  • Back installation of the connections
  • Unit dimension: (W x H x D) 1130 x 1306 x 886 mm

  • Balanced pad for installation on rough bottom
  • Cutting pipe to isolation of hydraulic connections
  • Electronic start
  • Regulator extension for:

    • Second heat circle e.g. for pool heater
    • Thermal  solar energy using
    • Two additional mixed circles

  • Low operating costs by high COP-values
  • Power adjustment by tandem compressors
  • Innovative controll software with mobil controll
  • Integration to internet possible
  • Display of current COP-values
  • Case in anthracite and white with tough powder coat

Effecient and economically together
The DS 5110T is used in multiple family houses or commercial buildings with low heating need. The achievement area of 48-112 kW is provided about the different construction dimensions. The highly efficient devices can be combined with closed earth probes or with open well systems over dividing heat exchanger.

High-class equipment
The standard equipment contains the innovative EasyCon software. The control of the arrangement is possible with it comfortably by means of Smartphone or professional service software.

Achievement on demand
The DS 5110T is equipped with two scroll compressors of the same achievement. The compressors can be pursued individually or together. Therefore an achievement gradation of 50% and 100% of the nominal achievement is possible. The biggest part of the operation duration can be covered with only one compressor and through this over again of improved efficiency.

Domestic water tank dock
By the connection of hot-water tank or heating buffer memories from the EcoStock series becomes the DS 5110T an entire heating system. To you memory dimensions stand standard according to demand from 200 to 1,000 litres for the choice.

+
Teaser
optionally: digital soft starter frequency converter
Item number
ET063500T
Persons
15
Flow temperature up to W10
63 °C
Flow temperature up to B0
63 °C
Power consumption input B0/W35
10.4 kW
Power consumption
W10/W35
Power consumption input
10.6 kW
Power consumption output
63.2 kW
Power consumption output B0/W35
47.6 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.70
COP EN14511 B0/W35
4.40
Groundwater flow rate
15.3 m³/h (Δt=3K)
Heatingwater flow rate
10.9 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W50, B0/W55, B5/W58, W10/W63
Heat source flow rate
11.90 m³/h (Δt=3K)
Unit weight
312 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R410A
+
Teaser
optionally: digital soft starter frequency converter
Item number
ET075500T
Persons
15
Flow temperature up to W10
63 °C
Flow temperature up to B0
55 °C
Power consumption input B0/W35
12 kW
Power consumption
W10/W35
Power consumption input
12.1 kW
Power consumption output
75.2 kW
Power consumption output B0/W35
56.6 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.90
COP EN14511 B0/W35
4.60
Groundwater flow rate
18.3 m³/h (Δt=3K)
Heatingwater flow rate
13 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W50, B0/W55, B5/W58, W10/W63
Heat source flow rate
14.30 m³/h (Δt=3K)
Unit weight
327 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R410A
Tank material
Stainless steel
+
Teaser
optionally: digital soft starter frequency converter
Item number
ET085500T
Persons
15
Flow temperature up to W10
63 °C
Flow temperature up to B0
55 °C
Power consumption input B0/W35
13.6 kW
Power consumption
W10/W35
Power consumption input
13.8 kW
Power consumption output
85 kW
Power consumption output B0/W35
64.2 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.90
COP EN14511 B0/W35
4.60
Groundwater flow rate
20.7 m³/h (Δt=3K)
Heatingwater flow rate
14.6 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W50, B0/W55, B5/W58, W10/W63
Heat source flow rate
16.20 m³/h (Δt=3K)
Unit weight
338 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R410A
+
Teaser
optionally: digital soft starter frequency converter
Item number
ET095500T
Persons
15
Flow temperature up to W10
63 °C
Flow temperature up to B0
55 °C
Power consumption input B0/W35
15.2 kW
Power consumption
W10/W35
Power consumption input
15.6 kW
Power consumption output
95.2 kW
Power consumption output B0/W35
71.4 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.80
COP EN14511 B0/W35
4.60
Groundwater flow rate
23 m³/h (Δt=3K)
Heatingwater flow rate
16.4 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W50, B0/W55, B5/W58, W10/W63
Heat source flow rate
18.00 m³/h (Δt=3K)
Unit weight
357 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R410A
Teaser
optionally: digital soft starter frequency converter
Item number
ET112500T
Persons
15
Flow temperature up to W10
63 °C
Flow temperature up to B0
55 °C
Power consumption input B0/W35
18.3 kW
Power consumption
W10/W35
Power consumption input
18.9 kW
Power consumption output
112.2 kW
Power consumption output B0/W35
84.6 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.60
COP EN14511 B0/W35
4.50
Groundwater flow rate
27 m³/h (Δt=3K)
Heatingwater flow rate
19.3 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W50, B0/W55, B5/W58, W10/W63
Heat source flow rate
21.20 m³/h (Δt=3K)
Unit weight
370 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R410A
+
Teaser
optionally: digital soft starter frequency converter
Item number
DS036400T
Persons
15
Flow temperature up to W10
75 °C
Flow temperature up to B0
75 °C
Power consumption input B0/W35
6.7 kW
Power consumption
W10/W35
Power consumption input
7.4 kW
Power consumption output
36.8 kW
Power consumption output B0/W35
26.3 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
4.90
COP EN14511 B0/W35
3.80
Groundwater flow rate
8.6 m³/h (Δt=3K)
Heatingwater flow rate
6.3 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W70, B0/W75, W10/W75, W15/W70
Heat source flow rate
6.30 m³/h (Δt=3K)
Unit weight
352 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R134a
+
Teaser
optionally: digital soft starter frequency converter
Item number
DS049400T
Persons
15
Flow temperature up to W10
75 °C
Flow temperature up to B0
75 °C
Power consumption input B0/W35
8.3 kW
Power consumption
W10/W35
Power consumption input
9.1 kW
Power consumption output
49.4 kW
Power consumption output B0/W35
35.8 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.30
COP EN14511 B0/W35
4.30
Groundwater flow rate
11.7 m³/h (Δt=3K)
Heatingwater flow rate
8.5 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W70, B0/W75, W10/W75, W15/W70
Heat source flow rate
8.80 m³/h (Δt=3K)
Unit weight
377 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R134a
+
Teaser
optionally: digital soft starter frequency converter
Item number
DS063400T
Flow temperature up to W10
75 °C
Flow temperature up to B0
75 °C
Power consumption input B0/W35
10.6 kW
Power consumption
W10/W35
Power consumption input
11.6 kW
Power consumption output
63 kW
Power consumption output B0/W35
45.4 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.30
COP EN14511 B0/W35
4.20
Groundwater flow rate
14.9 m³/h (Δt=3K)
Heatingwater flow rate
10.9 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W70, B0/W75, W10/W75, W15/W70
Heat source flow rate
11.20 m³/h (Δt=3K)
Unit weight
399 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R134a
+
Teaser
optionally: digital soft starter frequency converter
Item number
DS077400T
Persons
15
Flow temperature up to W10
75 °C
Flow temperature up to B0
75 °C
Power consumption input B0/W35
13 kW
Power consumption
W10/W35
Power consumption input
14.2 kW
Power consumption output
77.2 kW
Power consumption output B0/W35
55.4 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.30
COP EN14511 B0/W35
4.20
Groundwater flow rate
18.3 m³/h (Δt=3K)
Heatingwater flow rate
13.3 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W70, B0/W75, W10/W75, W15/W70
Heat source flow rate
13.60 m³/h (Δt=3K)
Unit weight
456 kg
Dimensions W x H x D
1100 x 1300 x 850 mm
Connections heat source/use
2 inch ext. flat-sealing
Refrigerant
R134a

Contact to Waterkotte

Send us your question.

Personal Guidance

Waterkotte Contact Person