Industrial Line EcoTouch 5240T | Geothermal heatpumps 20 - 300 kW

Hot waterVentilationCoolingHeatingSolar
Industrial Line EcoTouch 5240T - Geo heat pump 111-299 kW+
  • Heat pump for the average power requirement
  • Energy efficiency class A ++ / A +++
  • Two-stage power control
  • Integrated web interface for remote monitoring
  • Intuitively operable control software EasyCon
  • Sensor system with numerous sensors
  • COP counter and display of all operating data
  • Cascade control of up to 8 devices
  • Hot water preparation with external storage
  • Chlorine-free refrigerants R410A 
  • Signal for controlling the speed of the circulating pumps
  • Service-friendly device design
  • Rear mounting of the connections
  • Unit dimensions (W x H x D): 1130 x 1366 x 1076 mm
  • Balanced pad for installation on rough bottom
  • Cutting pipe to isolation of hydraulic connections
  • Frequency converter to eliminat starting current and for the progressive achievement adaptation
  • Regulator extension for:
    • Second heat circle e.g. for pool heater
    • Thermal  solar energy using
    • Two additional mixed circles
  • Low operating costs by high COP-values
  • Power adjustment by valve regulation or cylinder disconnection
  • Innovative controll software with mobil controll
  • Display of current COP-values
  • Case in anthracite and white with tough powder coat

Highest performance values
With an enormous power range of 57 - 299 kW, the ET 5240 series is ideally suited for use in buildings with high heating requirements. The power range is covered by the different sizes.

Flexible power control included
The ET 5240 series uses a variety of compressor techniques. A flexible, two-stage power control is carried out via the optional partial load control and with tandem units via the number of compressors.

Highest efficiency with minimal noise emission
The housing is complemented on the inside by a reliable airborne sound insulation. As a result, the operating volume is low. The L-shaped base frame minimizes transmitted solid-borne sound efficiency that you do not hear.

Innovative ease of use
The high-quality features include touch display, web interface and the innovative EasyCon software.

Item number
ET145501TAD-1
Persons
15
Flow temperature up to W10
64 °C
Flow temperature up to B0
60 °C
Power consumption input B0/W35
23.2 kW
Power consumption
W10/W35
Power consumption input
24 kW
Power consumption output
146.4 kW
Power consumption output B0/W35
111.1 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.62
COP EN14511 B0/W35
4.53
Groundwater flow rate
35.1 m³/h (Δt=3K)
Heatingwater flow rate
25.2 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W59, B0/W60, B5/W64, W10/W64
Heat source flow rate
27.8 m³/h (Δt=3K)
Unit weight
900 kg
Dimensions W x H x D
1130 x 1366 x 1076 mm
Connections heat source/use
2 1/2 inch ext. flat-sealing
Refrigerant
R410A
Item number
ET182501TAD-1
Persons
15
Flow temperature up to W10
64 °C
Flow temperature up to B0
60 °C
Power consumption input B0/W35
29.4 kW
Power consumption
W10/W35
Power consumption input
30.3 kW
Power consumption output
183.2 kW
Power consumption output B0/W35
140.3 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.7
COP EN14511 B0/W35
4.6
Groundwater flow rate
22 m³/h (Δt=3K)
Heatingwater flow rate
31.5 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W59, B0/W60, B5/W64, W10/W64
Heat source flow rate
35.1 m³/h (Δt=3K)
Unit weight
1000 kg
Dimensions W x H x D
1130 x 1366 x 1076 mm
Connections heat source/use
2 1/2 inch ext. flat-sealing
Refrigerant
R410A
Item number
ET235501TAD
Persons
15
Flow temperature up to W10
64 °C
Flow temperature up to B0
60 °C
Power consumption input B0/W35
37.4 kW
Power consumption
W10/W35
Power consumption input
38.7 kW
Power consumption output
238.1 kW
Power consumption output B0/W35
181.5 kW
Tank capacity min
200 l
Tank capacity max
1000 l
Tank capacity extentable
Yes
COP EN14511 W10/W35
5.7
COP EN14511 B0/W35
4.61
Groundwater flow rate
57.2 m³/h (Δt=3K)
Heatingwater flow rate
41 m³/h (Δt=5K)
Rolling piston inverter
Tandem fully hermetic scroll
Operating limit
B-5/W59, B0/W60, B5/W64, W10/W64
Heat source flow rate
45.6 m³/h (Δt=3K)
Unit weight
1100 kg
Dimensions W x H x D
1130 x 1366 x 1076 mm
Connections heat source/use
2 1/2 inch ext. flat-sealing
Refrigerant
R410A
Item number
ET300501TAD
Flow temperature up to W10
64 °C
Flow temperature up to B0
60 °C
Power consumption input B0/W35
47.2 kW
Power consumption
W10/W35
Power consumption input
50 kW
Power consumption output
299 kW
Power consumption output B0/W35
229 kW
COP EN14511 W10/W35
5.4
COP EN14511 B0/W35
4.52
Groundwater flow rate
72.3 m³/h (Δt=3K)
Heatingwater flow rate
51.5 m³/h (Δt=5K)
Operating limit
B-5/W59 B0/W60 B5/W64 W10 W64
Heat source flow rate
58 m³/h (Δt=3K)
Unit weight
1130 kg
Dimensions W x H x D
1130 x 1366 x 1076 mm
Connections heat source/use
flachdichtend G2 1/2"a / G 2 1/2"a
Refrigerant
R410A